Page view 11
Operating the Tool
User Guide AutroClient, Autroprime Interactive Fire Detection System, 116-P-APRIME2-AUTCLI/LGB, 2012-06-15,
Autronica Fire and Security AS
Page 12
4.3.4 Sound pattern
The AutroClient Sound pattern command is used to change the
default sound patterns.
4.3.5 Disable units
The AutroClient can be used to disable and enable units and loops.
The disable and enable buttons will be displayed when selecting a unit
or a loop. For units, the disable time can be set manually, the default
value being 60 seconds.
4.3.6 Activation test mode
The AutroClient can be used to activate outputs by setting them into
test mode. The detectors with LED will display an Activate LED button
when selected. When selected, the AutroClient will send an Activate
LED command to the Autroprime panel and the detector LED will be lit
for 10 seconds.
Figure 9. AutroClient displays control buttons for the selected detector.