Error! Unknown switch argument., AutroSafe Interactive Fire Alarm System, Release 3, P-ASAFE-LV/FE, Rev. A, 033105,
Autronica Fire and Security AS
Page 19
6. Examples of Special Topologies
6.1 Example 1: Break in Loop Wiring
In this example, the LoopViewer couldn’t find the ‘IN’ side of the Loop
driver, when powering up from the ‘OUT’ side. Since it can’t be known
which of the points LSI-4 or LSI-3.1 is the main loop, and which is the
branch, the LoopViewer presents a break symbol after both. The
LoopViewer will then power up the loop from the ‘IN’ side, and find the
points on the other side of the break. Note that if there is more than
one break in the main loop, there may be several points missing in the
loop topology presentation.