In the Event of Faults
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 37
8. In the Event of Faults
8.1 Indications in the Event of Faults
The yellow Fault indicator is pulsing.
The text display indicates the nature
of the fault. By operating the menu,
detailed information is available.
Depending on the nature of the
fault, and if configured and applied,
one or several of the following
yellow indicators may be pulsing:
- System Fault
- Annunciator Fault
- Remote Call Fault
The internal buzzer is activated.
8.2 Actions to be Taken in the Event of Faults
Step Actions to be
taken
Display Indication Audible Indication
1
Notify
service/technical
personnel if
necessary.
The internal buzzer on
the operator panel is
turned on.
Comments: The yellow Fault indicator is pulsing.
Depending on the nature of the fault, and if configured and applied, the
following indicators will be pulsing; System, Annunciator or Remote Call Fault.
2
To silence the internal
buzzer, press the
black
Mute Panel button.
The internal buzzer on
the operator panel is
turned off.
3
Use the arrow down
(/arrow up) button and
scroll to observe the
points in Fault state I
(if several).
A fault is indicated by one of the components (fire detectors, external equipment or
other faults).
Only the operating buttons that are available and
relevant to the current state are backlit.