Disabling
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 47
12.3 Disabling Activated / Deactivated Components
When you disable an active component, for example, a sounder
issuing an alarm signal, the component will immediately switch to the
OFF state without any user notification and/or confirmation cause.
A disablement of a deactivated component, for example, a sounder
not issuing an alarm signal, will have no immediate effect on system
operation.
Both activated and deactivated disabled components will remain
switched off until enabled.
12.4 Disabling Detection Zones
When you disable a Detection Zone - all points within the specified
detection zone will be disabled. A detection zone will not be indicated
as disabled unless all points within the zone have been disabled.
A disable time span can be set. When the disable time span expires,
the detection zone will automatically be enabled. The detection zone
can also be enabled manually from the Enable Menu.
12.5 Disabling Alarm Zones
When you disable an Alarm Zone all Fire Alarm Devices (FADs;
sounders, bells etc.) within the specified alarm zone will be disabled.
An alarm zone will not be indicated as disabled unless all Fire Alarm
Devices (FADs) within the alarm zone have been disabled.
A disable time span can be set. When the disable time span expires,
the alarm zone will automatically be enabled. The alarm zone can also
be enabled manually from the Enable Menu (or disablement window).
12.6 Disabling Points
When you disable a Point (fire detectors / manual call points), no
alarm signal or fault signal from this point will be sent in the event of
an alarm / fault.
A disable time span can be set. When the disable time span expires,
the point(s) will automatically be enabled. The point(s) can also be
enabled manually from the Enable Menu (or disablement window).