Enabling
Operator's Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-OPERATE/FGB Rev. B, 2009-10-28,
Autronica Fire and Security AS
Page 52
13.3 Enabling Deactivated Components
Setting the arm state of a disabled deactivated component to enabled
will have no immediate effect on system operation. The component
will remain deactivated until its activation state is set to an active state
(on alarm or on command).
13.4 Enabling Detection Zones
When you enable a Detection Zone, all points within the specified
detection zone will be enabled.
13.5 Enabling Alarm Zones
When you enable an Alarm Zone all Fire Alarm Devices (FADs;
sounders, bells etc.) within the specified alarm zone will be enabled,
except for those that are individually disabled as described in the
chapter 13.6 “Enabling Points”. An alarm zone will not be indicated as
enabled unless all Fire Alarm Devices (FADs) within the alarm zone
have been enabled.
13.6 Enabling Points
When a Point (fire detectors/manual call points) is enabled (manually
or when the disable time span expires), alarm signals will be sent from
this point in the event of an alarm, provided that there is no disable
source for the point.
13.7 Enabling Fire Alarm Devices
When you enable a Fire Alarm Device (FAD), the output which
controls the FAD will be enabled. The FAD will now give an audible
indication if it is still active.
You can enable a single unit (FAD)/alarm circuit, or all units (FADs) in
a selected Alarm Zone.