Maritime Installations
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 45
10.2 Fire Alarm Control Panel BS-200M
The BS-200M is specifically designed for use in maritime applications.
The panel is provided with a filter and a connection block for cable
connections.
10.2.1 External Connections
116-71211549 (230VAC) and
116-71211550 (110VAC)
X3 Description
1 Multifunction Serial Port RS-232 TX
External Interface optional data lines.
2 Multifunction Serial Port RS-232 RX
3 Multifunction Serial Port RS-232/422/485 0V
4 Multifunction Serial Port RS-422/485 A
5 Multifunction Serial Port RS-422/485 B
6 Multifunction Serial Port RS-422 Z
7 Multifunction Serial Port RS-422 X
8 Operator Panel Output +24V
Connections to Operator Panel (return/input for
redundancy).
9 Operator Panel Output 0V
10 Operator Panel Output A
11 Operator Panel Output B
12 Operator Panel Input +24V
13 Operator Panel Input 0V
14 Operator Panel Input A Connections to Operator Panel (Return/input for
redundancy). If no additional panels are connected to the
panel bus, return/input from operater panel at J4-18 and
J4-19.
15 Operator Panel Input B
16 BU/BV/Mimic Driver Output A
Connections to panel bus.
Connects from unit to unit (Return/input for redundancy).
17 BU/BV/Mimic Driver Output B
18 BU/BV/Mimic Driver Input A
19 BU/BV/Mimic Driver Input B
X2 Description
1 External 24V +
2 External 24V -
3 External 24V +
4 External 24V -
5 Battery 24V +
6 Battery 24V -
X1 Description
1 Mains 110/230 VAC
2 Mains 110/230 VAC
3 Emergency 110/230 VAC
4 Emergency 110/230 VAC
5 Earth
K15 Change-over Relay
K16 Mains Fault
K17 Emergency Fault
X2
X3
X