Changes on the Panel Bus
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 69
15.3 Removing a panel from the Panel Bus
Step Task Expected results
For example, a Fire Brigade Panel BU-210 is removed from the Panel Bus.
1
The system is to be in quiescent
condition.
Enter access level 3 (service
mode).
2
Remove a panel from the panel
bus by disconnecting the cables
from the panel.
Within 100 seconds the Fault indicator starts to pulse and the
internal buzzer is turned on.
The panel display shows the following message:
“Panel not responding”
“Communication redundancy lost”
“Configuration mismatch”
3
Press the Mute Panel button. The internal buzzer is turned off.
4
Acknowledge all the faults by
pressing the Function button,
select Acknowledge All, then
press Enter to accept.
The Fault indicator goes steady.
5
Connect the wires where the
break is.
6
Wait up to 100 seconds, then
press the Reset button.
The fault “communication redundancy lost” will disappear.
The faults “Panel not responding” and “Configuration
mismatch” will reappear.
7
Press the Mute Panel button The internal buzzer is turned off.
8
Acknowledge all the faults by
pressing the Function button,
select Acknowledge All, then
press Enter to accept.
The Fault indicator goes steady.
9
Save the configuration and restart
the system.
The system restarts.
The system starts in quiescent condition.
15.4 Replacing a panel of the same type and with the
same address
Step Task Expected results
For example, a Repeater Panel BS-211 is to be replaced by another Repeater Panel BS-211 with
the same address.
1
The system is to be in quiescent
condition.
Enter access level 3 (service
mode).
2
Replace a panel with another one
of the same type and the same
address.
Within 100 seconds the Fault indicator starts to pulse and the
internal buzzer is turned on.
3
Press the Mute Panel button. The internal buzzer is turned off.
4
Acknowledge the fault by pressing
the Function button, then press
the Enter button to accept.
The Fault indicator goes steady.