Changes on the Panel Bus
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 70
Step Task Expected results
5
Save the configuration and restart
the system.
The system restarts.
The system starts in quiescent condition.
15.5 Replacing a panel of the same type but with a
different address
Step Task Expected results
For example, a Repeater Panel BS-211 is to be replaced by another Repeater Panel BS-211 with a
different address.
1
The system is to be in quiescent
condition.
Enter access level 3 (service
mode).
2
Replace a panel with another one
of the same type but with a
different address (not used by any
other panels on the panel bus).
Within 100 seconds the Fault indicator starts to pulse and the
internal buzzer is turned on.
3
Press the Mute Panel button. The internal buzzer is turned off.
4
Acknowledge the fault by pressing
the Function button, then press
the Enter button to accept.
The Fault indicator goes steady.
5
Save the configuration and restart
the system.
The system restarts.
The system starts in quiescent condition.
15.6 Replacing a panel of a different type
Step Task Expected results
For example, a Repeater Panel BS-211 is to be replaced by an Information Panel BV-210.
1
The system is to be in quiescent
condition.
Enter access level 3 (service
mode).
2
Replace a panel with another one
of a different type.
Within 100 seconds the Fault indicator starts to pulse and the
internal buzzer is turned on. The panel display shows the
following message:
“Panel not responding”
“Configuration mismatch”
3
Press the Mute Panel button. The internal buzzer is turned off.
4
Acknowledge all the faults by
pressing the Function button,
select Acknowledge All, then
press Enter to accept.
The Fault indicator goes steady.
5
Save the configuration and restart
the system.
The system restarts.
The system starts in quiescent condition. The new panel is
operative.