Pre-installation
Installation Handbook, Autroprime Interactive Fire Detection System, 116-P-APRIME-INSTALL/DGB Rev. E, 2011-08-16,
Autronica Fire and Security AS
Page 8
2. Pre-installation
2.1 Location
The Fire Alarm Control Panel or Operator Panel must be located in, or
nearby, the entrance according to local regulations and in consultation
with the fire brigade.
Repeater Panels, Fire Brigade Panels and Information Panels must
be placed according to local regulations and in consultation with the
fire brigade.
2.2 Environmental Requirements
The equipment complies to environmental conditions of IEC-721-3-3
class 3k5.
Ambient temperature: -5 to +55 C
Degree of protection:
BS-200 and BS-200L: IEC-529/IP30
BS-200M: IEC-529/IP32
2.3 Mounting Height / Space Requirement
To ensure optimal readability of the panels’ display, the recommended
mounting height of the panel top is approximately 175 cm above the
floor.
2.4 Mounting Alternatives
The Fire Alarm Control Panel (BS-200, BS-200L, BS-200M) is to be
surface mounted onto the wall.
The Operator Panel (BS-210), which is an integrated part of the Fire
Alarm Control Panel, can also be mounted separately outside a
cabinet, either surface mounted onto the wall or mounted inside a 19’’
rack or console.
All other panel types; Repeater Panel (BS-211), Fire Brigade Panel
(BU-210), Information Panel (BV-210), Mimic Driver (BUR-200) and
the “Larmlagringspanel” BU-211 are to be surface mounted onto the
wall or mounted inside a 19’’ rack or console.
For information on mounting alternatives for the maritime panel
BS-200M and Mimic Cabinet BUR-200, refer to chapter 10.