Autronica BS-320 User's Guide Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 132
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
The Operator Panel - Overview
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 8
Fault
The yellow Fault Warning indicator shows the
presence of a fault within the operation zone of
the operator panel.
Blinking light
Unaccepted fault warnings exist.
Steady light
All fault warnings are accepted.
Function Disabled
Steady yellow light when one or more of the
following components within the operation zone of
the operator panel are in the disabled state:
function delayed
individual points
detection zones
alarm zones
Fire Alarm Devices, Fire Alarm Routing
Equipment, Fire Protection Equipment and
Fault Warning Routing Equipment.
2.2 Indication Devices
2.2.1 Upper Section
Power
Steady green light when power is ON.
Fire Brig. Signalled
Steady red light when the message is sent to the
Fire Brigade.
ALARM
The red alarm indicator shows that one or more
detection zones within the operating zone of the
Operator Panel are in the fire alarm state.
Blinking red light:
In the event of a fire alarm. The Fire Alarm
Devices (FAD) are still in active state.
Steady red light:
All FADs activated by the fire alarm condition
have been deactivated by operating the Silence
Alarms button. The control and indicating
equipment still remain in the fire alarm condition.
Power
Fire Brig. Signalled
Function Delayed
Function Disabled
ALARM
Mute Panel
Silence Alarms
Reset System
More Events
Fault
Text Display - See chapter 2.3.
Function Delayed
Steady yellow light indicates that Immediate Output
Actioning has been disabled (manual operation in
Menu Mode), i.e. a delay period is active for Fire
Alarm Devices (FAD) or Fire Alarm Routing
Equipment (FARE). Configurable.
More Events
In the event of more than one alarm.
The red More Events indicator shows that several
detection zones within an operating zone are in
the fire alarm state.
Blinking red light:
In the event of a fire alarm. The Fire Alarm
Devices (FAD) are still in active state.
Steady red light:
The Silence Alarms button has been pressed.
All
FADs activated by the fire alarm are no longer
active. The control and indicating equipment
still remain in the fire alarm condition.
Note that there are several national
variants of this panel. The
Indication Devices shown in this
handbook deals with
the Indication Devices for the
standard panel.