System Menu
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 83
13.9 Day / Night Timers
13.9.1 Starting / Stopping Automatic Day / Night
Operation from the Control Panel
From the Control Panel, it is possible to Start or Stop the automatic
day / night operation in the System Menu. After activation (Start) of
the automatic day/night operation, the affected Operation Zones will
be set to their correct state (Disabled or Enabled Immediate Output
Actioning) according to the specified schedules.
After deactivation (Stop) of the automatic day/night operation, the
affected Operation Zones will be left in its current state in respect to
Disabled/Enabled Immediate Output Actioning
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SYSTEM, press 4.
3
To select DAY/NIGHT TIMERS, press 7.
4
To select, press the relevant number (1-3):
1. Start
2. Stop
3. Show Running TImers
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
1 DATE AND TIME
2 INFORMATION
3 ACCESS LEVEL 3
4 PRINTER
5 CHANGE LANGUAGE
6 INITIALIZE
7 DAY/NIGHT TIMERS
19:23
SYSTEM
19:23
DAY/NIGHT TIMERS
1 START
2 STOP
3 SHOW RUNNING TIMERS
Execute command