Disabling
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 65
11.6 Disabling Points
When you disable a Point (fire detectors / manual call-points), no
alarm signal or fault signal from this point will be sent in the event of
an alarm / fault.
A disablement time can be set. When the disablement time expires,
the point(s) will automatically be enabled. The point(s) can also be
enabled manually from the Enable Menu.
If all points in a detection zone are disabled, the detection zone will be
indicated as disabled. If at least one point within this detection zone is
enabled manually, the detection zone will be indicated as enabled. If
the points are given different disablement times, the detection zone
will be automatically indicated as enabled when the first point is
enabled (i.e. when the point with the shortest disablement time is
enabled).
11.7 Disabling Fire Alarm Devices
When you disable a Fire Alarm Device (FAD), the output which
controls the FAD will be disabled. The FAD will thus give no audible
indication.
You can disable a single unit (FAD) / alarm circuit, or all units (FADs)
in a selected Alarm Zone.
A disablement time can be set. When the disablement time expires,
the FAD(s) will automatically be enabled. The single FAD or all FADs
in a selected Alarm Zone can also be enabled manually from the
Enable Menu.
11.8 Disabling Fire Alarm Routing Equipment
When you disable Fire Alarm Routing Equipment (FARE), the output
which controls such equipment will be disabled. In the event of an
alarm, no fire alarm signals / fault signals will be sent to the fire
brigade.
A disablement time can be set. When the disablement time expires,
the Fire Alarm Routing Equipment will automatically be enabled. The
equipment can also be enabled manually from the Enable Menu.
11.9 Disabling Outputs
When you disable outputs which control Fire Protection Equipment
(FPE), in the event of an alarm / fault, no signals will be sent to trigger
the equipment. You can disable a single output, or all outputs in the
Operation Zone.
A disablement time can be set. When the disablement time expires,
the outputs which control Fire Protection Equipment will automatically
be enabled. The outputs can also be enabled manually from the
Enable Menu.