Operation Mode
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 19
3.8 How to View Point Information
Note that the optional alarm presentation with zonal indication is
used throughout the handbook. The default alarm presentation
provides both zonal and point information.
To be able to select among detection zones in alarm, for example, «In
the Event of a Fire Alarm», you simply press the ENTER button ( ).
You can now use the up/down arrow buttons to select the wanted
zone.
FIRE ALARMS
19:23
Total: 3
1 OFFICES
2 CANTEEN
3 WORKSHOP
1: SHOW POINTS
19:23
Total: 3
To view points in alarm for the zone you have selected (highlighted),
you simply press digit 1 (SHOW POINTS, see Action Digits, 3.10),
and the following screen picture will appear (example):
SHOW STATUS
19:23
Total: 3
FIRE ALARMS/POINTS
1 OFFICES
Received 19:29:44
POINT: TYPE: STATUS:
P3 Heat Alarm
P5 Optical Alarm
FIRE ALARMS Total: 3
3 WORKSHOP
Last zone
in alarm
Total number
of zones in alarm
The point(s)
in alarm
The exact time
when the alarm
was received
The point
type
Here (in this example) you can view the points in alarm and the type
of point (detector type, manual call point). The arrow buttons are used
to move up and down in the list of points.
The close button ( ) is used to go one step backwards (at any time).
NOTE: If you have entered SHOW STATUS for information on points in alarm, you have
to press the Close button to re-enter Operation Mode in order to activate the Silence
Alarms button and the Reset button.