Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 101
14.4.1 Events
To be able to analyse system behaviour for service and maintenance
purposes, a number of events are recorded.
The table below gives an overview of these events and the detailed
information that can be shown on the panel’s display, or on a printout.
Event Detailed Information
Fire Alarms
• Date, time and identity of detection zones entering the Fire Alarm state.
Prealarms
• Date, time and identity of detection zones entering the Prealarm state.
Early Warnings
• Date, time and identity of detection zones entering the Early Warning state.
Faults
• Date, time and identity of subject (individual component, group, zone)
issuing a fault warning signal.
Enable/Disable
• Date, time and identity of subject (individual component, group, zone)
entering the disabled state.
• Date, time and identity of subject (individual component, group, zone)
exiting the disabled state.
User Operations
• The date, time and operation zone identity of the operation of push
buttons; RESET and SILENCE ALARMS.
• The date, time and operation zone identity of the operation of;
ALARM_DISABLE, REACTIVATE, RESOUND, INIT, ACTIVATE_ALARM,
ENABLE IMM_ACT, DISABLE_IMM ACT, SET_TIME.
• The date, time and event id (detection zone identity, fault identity etc) of all
operations of ACCEPT.
Tests
• Date, time and identity of all manually initiated tests.
All Events
• All events
Log Setup
• Read parameters, read filter, clear log.
Comments to this Manuals