Operation Mode
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 27
3.18.3 Coincidence Action Detection Zones
A fire alarm signal from a single detector in a Coincidence Action
detection zone, will initiate no actions, i.e. there will be no actioning of
outputs to;
Fire Alarm Devices (FAD)
Fire Alarm Routing Equipment (FARE)
Fire Protection Equipment (FPE)
- provided that FAD, FARE and FPE are set to Qualified Action (see
next page)
In the display, the alarm number for a detection zone will remain
steady until a new point in the same zone enters alarm state.
Note that the optional alarm presentation with zonal indication is
used throughout the handbook.
In the example below, the detection zone 2 CANTEEN is configured
as a zone with coincidence action.
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
Steady number (2) if only one detector
in this zone is in alarm state.
1 OFFICES
2 CANTEEN
3 WORKSHOP
FIRE ALARMS
19:23
Total: 3
Blinking number (2) if two or several
points or one manual call point in the
same zone are in alarm state.
Figure 3-7: Coincidence Action detection zone - indication
At least two detectors in the same detection zone must be in
alarm state before actions are initiated.
Note that an activation of a manual call-point in a coincidence
action detection zone will always initiate actions.