Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 92
14.3.2 Testing Outputs
14.3.2.1 Manual Test ON
The subsequent chapters describe how to test;
Fire Alarm Devices (FAD)
Fire Alarm Routing Equipment (FARE)
Fire Warning Routing Equipment (FWRE)
Other Outputs
Outputs activated by “Manual Test ON” will be kept active, i.e. reset
will not deactivate. An ongoing test can be terminated by use of the
Manual Test OFF menu.
14.3.2.2 Manual Test ON- Fire Alarm Devices (FAD)
This chapter describes how to test Fire Alarm Devices. The test
requires Access Level 3 (password restricted).
When the test is initiated, a test signal will be sent to all Fire Alarm
Devices within the selected Alarm Zone. The duration of the signal
and the interval between each signal are configurable (normally 1
second ON and 30 seconds OFF).
The test signal is given the lowest priority. In the event of an alarm,
the alarm signal will thus override the test signal.
Step Actions to be taken Display Indication
1
To enter the Main Menu, press
MENU
19:23
Total: 3
1 SHOW STATUS
2 DISABLE
3 ENABLE
4 SYSTEM
5 SERVICE
2
To select SERVICE, press 5.
SERVICE
19:23
1 TEST
2 LOG
3 LOOP COMMANDS
4 REPORT